KPN5500-030 - Bar Graph Temperature Controllers

model * Image may differ
CAD

KPN5500-030

  • Power supply : 100-240VAC~ 50/60Hz
  • Input type_RTD : JPt100Ω, DPt100Ω, DPt50Ω, Cu100Ω, Cu50Ω, Nikel120Ω (6 types)
  • Input type_TC : K, J, E, T, L, N, U, R, S, B, C, G, PLII (13 types)
  • Input type_Analog : ㆍVoltage: 0-100mV, 0-5 V, 1-5 V, 0-10 V (4 types) ㆍCurrent: 0-20mA, 4-20mA (2 types)
  • Control method : ON/OFF, P, PI, PD, PID
  • Protection structure : IP65(front panel)
  • Control output : Selectable Relay output, Current output, SSR drive output
  • Environment_Ambient temperature : -10 to 50℃, storage: -20 to 60℃
certmark certmark certmark certmark

Data sheet Print

Data sheet
Power supply 100-240VAC~ 50/60Hz
Input type_RTD JPt100Ω, DPt100Ω, DPt50Ω, Cu100Ω, Cu50Ω, Nikel120Ω (6 types)
Input type_TC K, J, E, T, L, N, U, R, S, B, C, G, PLII (13 types)
Input type_Analog ㆍVoltage: 0-100mV, 0-5 V, 1-5 V, 0-10 V (4 types) ㆍCurrent: 0-20mA, 4-20mA (2 types)
Control method ON/OFF, P, PI, PD, PID
Sampling cycle 50ms
Protection structure IP65(front panel)
Size DIN W96×H96mm
The number of control ouptut 1 output type(Heating or Cooling type)
Control output Selectable Relay output, Current output, SSR drive output
Option communication output None
Option input/output Transmission output+Remote SV
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Weight Approx. 316g(approx. 220g)

※The 1 output type is heating or cooling output type and the 2 output type is heating & cooling output type.
The 1 output type is able to use only one output among relay output, current output, SSR drive output.
OUT1 of the 2 output type is fixed as heating output and OUT2 of the 2 output type is fixed as cooling output.
If you select the SSR drive output or current output model, you can select the appropriate control output.
※Displayaccuracy:
◎At room temperature (23℃±5℃)
ㆍTC K, J, T, N, E type, below -100℃ / L, U, PLⅡ, RTD Cu50, DPt50: (PV ±0.3% or ±2℃, select the higher one) ±1digit
ㆍTC C, G and R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1digit
ㆍTC B type, below 400℃, there is no accuracy standards.
◎Out of room temperature range
ㆍRTD Cu50, DPt50: (PV 0.5% or ±3℃, select the higher one) ±1digit
ㆍRTD R, S, B, C, G: (PV ±0.5% or ±10℃, select the higher one) ±1digit
ㆍOther sensors: below -100℃, within ±5℃
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

3D Viewer

* You can check out the 3D Viewer by the CAD button under the product image.

PR materials

PR materials can be downloaded without login.
  • {{result.bbsCtgryNm}}
    {{result.nttSj}}
    Language selection
    Downloads Preview

Technical dataView more

3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
  • No search results

Recently viewed product(s)

View more

There are no recently viewed product(s)

Interested product(s)

View more

Compare products

View more

Download history

View more

Product Inquiry