SFC-R212 - Safety Relay Units
* Image may differ
SFC-R212
- Power supply : 24VDC@(=)
- Power consumption : 4.0W
- Input : ON: ≥11 VDC@(=) ≥ 5mA, OFF: ≤ 5VDC@(=) ≤ 1mA
- Safety output : Relay (A contact)
- Sub output : 1 × PNP transistor: X1
Data sheet Print
Power supply | 24VDC@(=) |
---|---|
Allowable voltage range | 85 to 110% of rated voltage |
Power consumption | 4.0W |
Input | ON: ≥11 VDC@(=) ≥ 5mA, OFF: ≤ 5VDC@(=) ≤ 1mA |
Input time | ≥ 50ms, feedback start (manual) : ≥ 100ms |
Cable | ≤ 100m (≤ 100Ω, ≤ 10nF) |
Safety output | Relay (A contact) |
Instantaneous | 2 × |
Capacity | 240 VAC~ 5A, 30 VDC@(=) 5A |
Life expectancy | Mechanical: ≥ 10,000,000 operations, Malfunction: ≥ 50,000 operations |
Contact resistance | ≤ 100mΩ |
Inductive load switching | IEC60947-5-1: AC-15 (230 V/2 A), DC-13 (24 V/1.5 A), UL508: B300/R300 |
Conditional short circuit current | 100A |
Sub output | 1 × PNP transistor: X1 |
Load current | Max. 100mA |
Leakage current | ≤ 0.1mA |
International standards | IEC/EN 61508 (SIL3), IEC/EN 62061 (SILCL3) IEC/EN 60947-5-1, EN ISO 13849-1 (Category 4, PLe) UL listed E249635 |
Weight | Approx. 80g (approx. 130g) |
3D Viewer
* You can check out the 3D Viewer by the CAD button under the product image.
PR materials
PR materials can be downloaded without login.
Technical dataView more
3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
- No search results
-
- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}