TK4M-14SN - High Performance PID Temperature Controllers
TK4M-14SN
- Display method : 4-digit 7-segment LED
- Control method : ON/OFF, P, PI, PD, PID
- Input specification : Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel IIRTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120ΩAnalog: 0-100mV, 0-5V, 1-5V, 0-10V0-20mA, 4-20mA
- Sampling cycle : 50ms
- Control output 1 : SSR drive(11VDC @(=)) [ON/OFF, phase, cycle]
- Option output : Alarm 1
- Power supply : 100-240VAC~ 50/60Hz
- Protection structure : IP65(front panel)
Data sheet Print
Display method | 4-digit 7-segment LED |
---|---|
Control method | ON/OFF, P, PI, PD, PID |
Input specification | Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel IIRTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120ΩAnalog: 0-100mV, 0-5V, 1-5V, 0-10V0-20mA, 4-20mA |
Sampling cycle | 50ms |
Control output 1 | SSR drive(11VDC @(=)) [ON/OFF, phase, cycle] |
Option input | CT, Digital(DI-1) |
Option output | Alarm 1 |
Power supply | 100-240VAC~ 50/60Hz |
Protection structure | IP65(front panel) |
Display accuracy_RTD | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit |
Display accuracy_Thermocouple | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit |
Display accuracy_Analog | •At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit•Out of range of room temperature: ±0.5℃% F.S. ±1-digit |
Display accuracy_CT input | ±5% F.S. ±1-digit |
Hysteresis(adjustable sensitivity) | RTD/Thermocouples: 1 to 100℃/℉(0.1 to 100.0℃/℉) variable Analog: 1 to 100-digit |
Proportional band | 0.1 to 999.9℃/℉(0.1 to 999.9%) |
Integral time | 0 to 9999 sec |
Derivative time | 0 to 9999 sec |
Control period | Relay output, SSR drive output: 0.1 to 120.0 sec Current output or SSR drive output selectable: 1.0 to 120.0 sec |
Manual reset | 0.0 to 100.0% |
Environment_Ambient temperature | -10 to 50℃, storage: -20 to 60℃ |
Environment_Ambient humidity | 35 to 85% RH, storage: 35 to 85% RH |
Insulation type | Double insulation or reinforced insulation(mark: @(INS), dielectric strength between the measuring input part and the power part: 2kV) |
Weight | Approx. 210g(approx. 140g) |
※“S” represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are available. “C” represents selectable current and SSR drive output support models.※Select "R" or "C" type in case of using heating&cooling control and "N" type in case of using standard control.※Does not support in AC/DC voltage type model.※CT input of TK4N is available only for the standard model which has alarm output 1.※Display accuracy: ◎At room temperature (23℃±5℃)• Thermocouple K, J, T, N, E type, below -100℃/Thermocouple L, U, PLⅡ type, RTD Cu50Ω, DPt50Ω: (PV ±0.3% or ±2℃, select the higher one) ±1-digit• Thermocouple C, G, R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1-digit• Thermocouple B type, below 400℃: there is no accuracy standards.◎Out of room temperature range• RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit• Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5℃, select the higher one) ±1-digit• Others, Below -100℃: within ±5℃In case of TK4SP Series, ±1℃ will be added to the degree standard.※The weight includes packaging. The weight in parenthesis is for unit only.※Environment resistance is rated at no freezing or condensation.
3D Viewer
* You can check out the 3D Viewer by the CAD button under the product image.
PR materials
Technical dataView more
- No search results
-
- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}