TK4W-A4RN - High Performance PID Temperature Controllers
TK4W-A4RN
- Display method : 4-digit 7-segment LED
- Control method : ON/OFF, P, PI, PD, PID
- Input specification : Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel IIRTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120ΩAnalog: 0-100mV, 0-5V, 1-5V, 0-10V0-20mA, 4-20mA
- Sampling cycle : 50ms
- Control output 1 : Relay(250VAC~ 3A)
- Option output : Alarm 1/2, Transmission(DC4-20mA)
- Power supply : 100-240VAC~ 50/60Hz
- Protection structure : IP65(front panel)
Data sheet Print
Display method | 4-digit 7-segment LED |
---|---|
Control method | ON/OFF, P, PI, PD, PID |
Input specification | Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel IIRTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120ΩAnalog: 0-100mV, 0-5V, 1-5V, 0-10V0-20mA, 4-20mA |
Sampling cycle | 50ms |
Control output 1 | Relay(250VAC~ 3A) |
Option input | CT, Digital(DI-1/2) |
Option output | Alarm 1/2, Transmission(DC4-20mA) |
Power supply | 100-240VAC~ 50/60Hz |
Protection structure | IP65(front panel) |
Display accuracy_RTD | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit |
Display accuracy_Thermocouple | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit |
Display accuracy_Analog | •At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit•Out of range of room temperature: ±0.5℃% F.S. ±1-digit |
Display accuracy_CT input | ±5% F.S. ±1-digit |
Hysteresis(adjustable sensitivity) | RTD/Thermocouples: 1 to 100℃/℉(0.1 to 100.0℃/℉) variable Analog: 1 to 100-digit |
Proportional band | 0.1 to 999.9℃/℉(0.1 to 999.9%) |
Integral time | 0 to 9999 sec |
Derivative time | 0 to 9999 sec |
Control period | Relay output, SSR drive output: 0.1 to 120.0 sec Current output or SSR drive output selectable: 1.0 to 120.0 sec |
Manual reset | 0.0 to 100.0% |
Environment_Ambient temperature | -10 to 50℃, storage: -20 to 60℃ |
Environment_Ambient humidity | 35 to 85% RH, storage: 35 to 85% RH |
Insulation type | Double insulation or reinforced insulation(mark: @(INS), dielectric strength between the measuring input part and the power part: 2kV) |
Weight | Approx. 211g(approx. 141g) |
※“S” represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are available. “C” represents selectable current and SSR drive output support models.※Select "R" or "C" type in case of using heating&cooling control and "N" type in case of using standard control.※CT input of TK4N is available only for the standard model which has alarm output 1.※Display accuracy: ◎At room temperature (23℃±5℃)• Thermocouple K, J, T, N, E type, below -100℃/Thermocouple L, U, PLⅡ type, RTD Cu50Ω, DPt50Ω: (PV ±0.3% or ±2℃, select the higher one) ±1-digit• Thermocouple C, G, R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1-digit• Thermocouple B type, below 400℃: there is no accuracy standards.◎Out of room temperature range• RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit• Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5℃, select the higher one) ±1-digit• Others, Below -100℃: within ±5℃In case of TK4SP Series, ±1℃ will be added to the degree standard.※The weight includes packaging. The weight in parenthesis is for unit only.※Environment resistance is rated at no freezing or condensation.
3D Viewer
* You can check out the 3D Viewer by the CAD button under the product image.
PR materials
Technical dataView more
- No search results
-
- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}
Used together with
-
SPC1 Series
The SPC1 series single phase power controllers offer reliable and stable power control. The units can handle various control inputs and feature various control modes (phase control, cycle control, ON/OFF control). The controllers also feature various functions including output adjustment function and soft start function. Users can also quickly identify operation status with the LED output operation indicator.
-
SPR1 Series
The SPR1 series single-phase power controllers are ideal for installation in limited spaces with slim body sizes measuring only 55 mm wide. The LED display allows real-time monitoring of control input, load voltage, load current, load power, load resistance, and heat-sink temperature. The controllers feature phase control, cycle control, and ON/OFF control methods, with feedback control (constant current, constant voltage, constant power) option available for accurate and stable power control.