TNS-P42CR-NS-006 - 2-DOF PID Temperature Controllers (Program/Fixed Control)
* Image may differ
TNS-P42CR-NS-006
- Power supply : 100-240VAC~ 50/60Hz
- Control output_Relay : 250VAC~ 3A 1a
- Control output_Current : DC 0 - 20 mA or DC 4 - 20 mA (parameter), Load resistance: ≤ 500 Ω
- Option output_Alarm : 250VAC~ 3A 1a
- Program control_Program : ≤ 10 patterns
- Loader port : Top side
Data sheet Print
Power supply | 100-240VAC~ 50/60Hz |
---|---|
Power consumption | Max. 8VA |
Display method | 11 segment, LCD type (operating value display part: 7 segment) |
Sampling cycle | 50 / 100 / 250 ms (parameter) |
Option input_CT input | • 0.0-50.0 A (primary current measurement range)• CT ratio: 1/1 |
Control output_Relay | 250VAC~ 3A 1a |
Control output_Current | DC 0 - 20 mA or DC 4 - 20 mA (parameter), Load resistance: ≤ 500 Ω |
Option output_Alarm | 250VAC~ 3A 1a |
Control type_Type | ON/OFF, P, PI, PD, PID |
Control type_Multi SV | ≤ 4 SV |
Control type_Group PID | ≤ 8 group |
Control type_Zone PID | 4 zones |
Control type_ARW | 50 to 200 % |
Program control_Program | ≤ 10 patterns |
Program control_Step | ≤ 200 steps (1 pattern: ≤ 20 steps) |
Program control_Setting type | Time setting |
Hysteresis | • Thermocouple, RTD: 1 to 100 (0.1 to 100.0) ℃/℉• Analog: 1 to 100 digit |
Dielectric strength | Between primary terminal and case: 3,000 VAC~ 50/60 Hz for 1 min |
Vibration | 0.75 mm amplitude at frequency of 5 to 55 Hzin each X, Y, Z direction for 2 hours |
Relay life cycle_Mechanical | • OUT1/2: ≥ 5,000,000 operations• AL1/2/3/4/5/6: ≥ 20,000,000 operations |
Relay life cycle_Electrical | • OUT1/2: ≥ 200,000 operations• AL1/2/3/4/5/6: ≥ 100,000 operations |
Insulation resistance | ≥ 100 MΩ (500 VDC@(=) megger) |
Insulation type | Double insulation or reinforced insulation (mark: @(INS), dielectric strength between the measuring input part and the power part: 3 kV) |
Noise immunity | ±2 kV square shaped noise by noise simulator (pulse width: 1 ㎲) R-phase, S-phase |
Memory Protection | ≈ 10 years (non-volatile semiconductor memory type) |
Ambient temperature | -10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation) |
Ambient humidity | 35 to 85%RH |
Protection structure | IP65 (Front panel, IEC standards) |
Loader port | Top side |
Accessories | Bracket |
Weight | 128 g |
3D Viewer
* You can check out the 3D Viewer by the CAD button under the product image.
PR materials
PR materials can be downloaded without login.
Technical dataView more
3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
- No search results
-
- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}