TX4S-14R - LCD Display PID Temperature Controllers

model * Image may differ
CAD

TX4S-14R

  • Display method : 4-digit 11-segment LCD
  • Control method : ON/OFF, P, PI, PD, PID
  • Input specification : Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
    RTD: DPt100Ω, Cu50Ω
  • Sampling cycle : 50ms
  • Control output : Relay (250VAC~ 3A, 30VDC @(=) 3A)
certmark certmark certmark certmark certmark certmark

Data sheet Print

Data sheet
Display method 4-digit 11-segment LCD
Control method ON/OFF, P, PI, PD, PID
Input specification Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle 50ms
Control output Relay (250VAC~ 3A, 30VDC @(=) 3A)
Option output Alarm 1
Power supply 100-240VAC~ 50/60Hz
Protection structure IP50(front panel)
Display accuracy_RTD •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Thermocouple •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Hysteresis(adjustable sensitivity) 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band 0.1 to 999.9℃/℉
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Insulation type Double insulation (mark: @(INS), dielectric strength between primary circuit and secondary circuit: 3kV)
Weight Approx. 146.1g(approx. 86.7g)

※When using the unit at low temperature (below 0℃), display cycle is slow. Control output operates normally.
※◎ At room temperature(23℃±5℃)
TC R(PR), S(PR) , below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit, over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
◎ Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

3D Viewer

* You can check out the 3D Viewer by the CAD button under the product image.

PR materials

PR materials can be downloaded without login.
  • {{result.bbsCtgryNm}}
    {{result.nttSj}}
    Language selection
    Downloads Preview

Technical dataView more

3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
  • No search results

Recently viewed product(s)

View more

There are no recently viewed product(s)

Interested product(s)

View more

Compare products

View more

Download history

View more

Product Inquiry