TR1D-T4CC - Slim Single Display PID Temperature Controllers
TR1D-T4CC
- Power supply : 100-240VAC~ 50/60Hz
- Allowable voltage range : 90 to 110% of rated voltage
- Power consumption : Max. 8VA
- Control output_SSR : Max. 12VDC @(=) ±3V 20mA
- Control output_Current : Selectable DC 4-20mA or DC 0-20mA(load resistance max. 500Ω)
- Option output_Trans. : DC 4 - 20 mA (load resistance: ≤ 500 Ω, output accuracy: ±0.3% F.S.)
- Option output_Comm. : RS485 communication output (Modbus RTU/ASCII method)
Data sheet Print
Power supply | 100-240VAC~ 50/60Hz |
---|---|
Allowable voltage range | 90 to 110% of rated voltage |
Power consumption | Max. 8VA |
Sampling cycle | 50, 100, 250ms |
Input type_RTD | DPt100Ω, Cu50Ω, Nickel120Ω (permissible line resistance max. 5Ω) |
Input type_TC | K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) |
Input type_CT | 0.0-50.0A(primary current measurement range) ※CT ratio=1/1000 |
Display accuracy | RTD/Thermocouple: ㆍ At room temperature (23℃ ±5℃): (PV ±0.3% or ±1℃, select the higher one) ±1-digitㆍ Out of room temperature ranges: (PV ±+H400.5% or ±2℃, select the higher one) ±1-digit |
Display accuracy_CT input | ±5% F.S. ±1-digit |
Control output_SSR | Max. 12VDC @(=) ±3V 20mA |
Control output_Current | Selectable DC 4-20mA or DC 0-20mA(load resistance max. 500Ω) |
Option output_Trans. | DC 4 - 20 mA (load resistance: ≤ 500 Ω, output accuracy: ±0.3% F.S.) |
Option output_Comm. | RS485 communication output (Modbus RTU/ASCII method) |
Display method | 7-segment (red) 4-digit |
Control method | ON/OFF, P, PI, PD, PID |
Control output_Hysteresis | Control output: 1 to 100℃/℉ (0.1 to 100.0℃/℉)Alarm output: 1 to 100℃/℉ (0.1 to 50.0℃/℉) |
Proportional band | 0.1 to 999.9℃ |
Integral time | 0 to 9999 sec |
Derivative time | 0 to 9999 sec |
Control period | Relay output: 0.5 to 120.0 sec, SSR output: 0.5 to 120.0 sec |
Dielectric strength | Between the charging part and the case : 3,000 VAC~ 50/60 Hz for 1 min |
Vibration | 0.75 mm amplitude at frequency of 5 to 55 Hzin each X, Y, Z direction for 2 hours |
Relay life cycle_Mechanical | OUT1/2, AL1/2: min. 5,000,000 operations |
Relay life cycle_Electrical | OUT1/2, AL1/2: min. 100,000 (resistance load: 250VAC~ 5A) |
Insulation resistance | 100MΩ or more (500VDC megger basis) |
Insulation type | Double insulation or reinforced insulation (dielectric strength between the charging part and the case: 3 kV) |
Noise immunity | ±2 kV square shaped noise by noise simulator (pulse width: 1 ㎲) R-phase, S-phase |
Memory Protection | ≈ 10 years (non-volatile semiconductor memory type) |
Environment_Ambient temperature | -10 to 50℃, storage: -20 to 60℃ |
Environment_Ambient humidity | 35 to 85% RH, storage: 35 to 85% RH |
Weight | Approx. 194.5g (approx. 123.5g) |
3D Viewer
* You can check out the 3D Viewer by the CAD button under the product image.
PR materials
Technical dataView more
- No search results
-
- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}- {{ result.parntsBbsCtgryNm }}
- {{ result.bbsCtgryNm }}
{{ result.nationAtchVoList[0].extension }} {{ result.nttSj }}
Used together with
-
BEST
SCM Series
The SCM series communication converters are available in various types, to offer easy signal conversion and flexibility for building diverse systems. Wireless, USB-RS485, RS232C-RS485, and USB-Serial converters are available.
-
UPGRADE BEST
DAQMaster
DAQMaster is a comprehensive device management software used to configure parameters, monitor real-time data, and store data with communication supported devices from Autonics. Simple GUI control allows easy and convenient management of parameters and data monitoring of multiple devices. DAQMaster is available in Standard (free) and Pro (paid) versions for PCs.