Recommended browsers

Please use Internet Explorer 10 or above for optimal viewing experience on the Autonics website.

When using Internet Explorer 10 or earlier, 3D CAD viewer and screen layout may not be displayed normally.
For ease of use the site, we recommend upgrading to a modern browser.

browser img

TX4S-24C - LCD Display PID Temperature Controllers

model * Image may differ
CAD

TX4S-24C

  • Display method : 4-digit 11-segment LCD
  • Control method : ON/OFF, P, PI, PD, PID
  • Input specification : Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
    RTD: DPt100Ω, Cu50Ω
  • Sampling cycle : 50ms
  • Control output : Current (DC0/4-20mA) or SSR drive (13VDC @(=))[ON/OFF]
certmark certmark certmark certmark certmark certmark

Data sheet Print

Data sheet
Display method 4-digit 11-segment LCD
Control method ON/OFF, P, PI, PD, PID
Input specification Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle 50ms
Control output Current (DC0/4-20mA) or SSR drive (13VDC @(=))[ON/OFF]
Option output Alarm 1/2
Power supply 100-240VAC~ 50/60Hz
Protection structure IP50(front panel)
Display accuracy_RTD •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Thermocouple •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Hysteresis(adjustable sensitivity) 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band 0.1 to 999.9℃/℉
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Insulation type Double insulation (mark: @(INS), dielectric strength between primary circuit and secondary circuit: 3kV)
Weight Approx. 146.1g(approx. 86.7g)

※When using the unit at low temperature (below 0℃), display cycle is slow. Control output operates normally.
※◎ At room temperature(23℃±5℃)
TC R(PR), S(PR) , below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit, over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
◎ Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

3D Viewer

* You can check out the 3D Viewer by the CAD button under the product image.

PR materials

PR materials can be downloaded without login.
  • {{result.bbsCtgryNm}}
    {{result.nttSj}}
    Language selection
    Downloads Preview

Technical dataView more

3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
  • No search results

Recently viewed product(s)

View more

There are no recently viewed product(s)

Interested product(s)

View more

Compare products

View more

Download history

View more

Product Inquiry