M4NN-DA-1N

  • Display method : 4-digit 7-segment LED
  • Character height : 11mm
  • Max. display Range : -1999 to 9999
  • Measurement : DC current
  • Input specification : -5-5A, -2-2A, -1-1A, -200-200mA, -100-100mA, -20-20mA, 4-20mA, -10-10mA, -2-2mA
  • Power supply : 5-24VDC @(=)
certmark certmark certmark certmark

Data sheet Print

Data sheet
Display method 4-digit 7-segment LED
Character height 11mm
Max. display Range -1999 to 9999
Measurement DC current
Input specification -5-5A, -2-2A, -1-1A, -200-200mA, -100-100mA, -20-20mA, 4-20mA, -10-10mA, -2-2mA
Power Factor Display Power Factor Display
Power supply 5-24VDC @(=)
Output_Main Output(Comparative Value) Indicator
Max. allowable input -110 to 110% of the rated measurement input range(when not using minus input: -10 to 110%)
Display accuracy •23℃±5℃ - ±0.1% F.S. ±2-digit
※For 5A terminal of M4NN-DA, AA Input, ±0.3% F.S. ±3-digit
•-10 to 50℃ - ±0.5% F.S. ±3-digit
※For 5A terminal of M4NN-DA, AA Input, ±1% F.S. ±3-digit
Display cycle 0.1 to 5.0 sec (selectable by 0.1 sec)
A/D conversion method Practical oversampling using successive approximation ADC
Sampling cycle 50ms (resolution 1/12,000)
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Insulation type Double insulation or reinforced insulation(mark: @(INS), dielectric strength between the measuring input part and the power part: 1kV)
Protection structure IP53 (front part, IEC standard)
Weight Approx. 83.7g(approx. 46.7g)

※Indicator (M4NN-□□-1N) model does not have output function.
※AC, frequency measurement functions are only for AC measurement type.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

3D Viewer

* You can check out the 3D Viewer by the CAD button under the product image.

PR materials

PR materials can be downloaded without login.
  • {{result.bbsCtgryNm}}
    {{result.nttSj}}
    Language selection
    Downloads Preview

Technical dataView more

3D drawings for each detailed model can be checked and downloaded from the model page at the bottom.
  • No search results

Recently viewed product(s)

View more

There are no recently viewed product(s)

Interested product(s)

View more

Compare products

View more

Download history

View more

Product Inquiry