Recommended browsers

Please use Internet Explorer 10 or above for optimal viewing experience on the Autonics website.

When using Internet Explorer 10 or earlier, 3D CAD viewer and screen layout may not be displayed normally.
For ease of use the site, we recommend upgrading to a modern browser.

browser img

MX4W-A-FN - LCD Display Multi Panel Meter

model * Image may differ
CAD

MX4W-A-FN

  • Display method : 12 segment (measurement value display part: white, character height: 19mm), other display parts(red, green, yellow, indicator model: white) LCD method
  • Character height : 19mm
  • Max. display Range : -9999 to 9999(4digit)
  • Measurement : DC current
    AC current, Frequency
  • Input specification : DC ±20mA, 4-20mA, ±5mA, ±2mA, ±500mA, ±200mA, ±50mA, ±5A, ±2A,
    AC 0-20mA, 0-5mA, 0-2mA, 0-500mA, 0-200mA, 0-50mA, 0-5A, 0-2A
  • Power supply : 24-240VAC~ 50/60Hz, 24-240VDC @(=)
  • Environment_Ambient temperature : -10 to 50℃, storage: -20 to 60℃
  • Weight : Approx. 100g(approx. 77g)
certmark certmark certmark certmark certmark

Data sheet Print

Data sheet
Display method 12 segment (measurement value display part: white, character height: 19mm), other display parts(red, green, yellow, indicator model: white) LCD method
Character height 19mm
Max. display Range -9999 to 9999(4digit)
Measurement DC current
AC current, Frequency
Input specification DC ±20mA, 4-20mA, ±5mA, ±2mA, ±500mA, ±200mA, ±50mA, ±5A, ±2A,
AC 0-20mA, 0-5mA, 0-2mA, 0-500mA, 0-200mA, 0-50mA, 0-5A, 0-2A
AC Measurement Select RMS value /AVG value measurement methods
Power Factor Display Power factor display are available when input type is DC.
Power supply 24-240VAC~ 50/60Hz, 24-240VDC @(=)
Output_Main Output(Comparative Value) Indicator
Max. allowable input • DC input: approx. -110 to 110% of each measurement input range(when not using minus input: -10 to 110%)
• AC input: approx. 110% of each measurement input range
Display accuracy 23±5℃ - DC input: ±0.1% F .S. ±2digit, AC input: ±0.3% F .S. ±3digit
※The teminal for 5A of current input, ±0.3% F .S. ±3digit,
0~50℃ - AC/DC input: ±0.5% F .S. ±3digit
※The teminal for 5A of current input, ±1% F .S. ±3digit
Display cycle 0.2 to 5.0 sec (select per 0.1 sec)
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Protection structure IP54 (front part, IEC standard)
Weight Approx. 100g(approx. 77g)

※Display method: When using the unit at low temperature(below 0℃), display cycle is slow due to characteristics of LCD. Control output operates normally.
※Preset output: indicator model(MX4W-□-FN) dose not have the function.
※AC, frequency measurment are available when input type is AC
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

3D Viewer

* You can check out the 3D Viewer by the CAD button under the product image.

PR materials

PR materials can be downloaded without login.
  • {{result.bbsCtgryNm}}
    {{result.nttSj}}
    Language selection
    Downloads Preview

Technical dataView more